Product Description
Part Number: 1746-OA16
Estimated Lead Time: 6 - 8 Shipping Weight: 2 Kg
| Model | 1746-OA16? | |
| Voltage category | 120/240V AC signal input | |
| Number of outputs | 16 | |
| Points per common | 8 | |
| Voltage, operating | 85...265V AC @ 47...63 Hz | |
| Backplane current consumption | 5V DC | 0.370 A |
| 24V DC | 0.0 A | |
| Signal delay, max resistive load? | On = 1 ms Off = 11.0 ms | |
| Off-state voltage, max? | 2 mA | |
| Off-state current, max | 2 mA | |
| Input current | 12 mA @ 120V AC, nom | |
| Inrush current, max? | 0.8 A | |
| Inrush current time duration, max | 0.5 ms | |
(1) Triac outputs turn on at any point in the AC line cycle, and turn off at AC line zero cross.
(2) To limit the effects of leakage current through solid-state outputs, a loading resistor can be connected in parallel with your load.
For 120V AC operation, use a 15 K , 2 W resistor. For 240V AC operation, use a 15 K , 5 W resistor.
(3) Removable terminal block.