Product Description
Part Number : 1756-IM16I
Availability : In Stock Estimated Lead Time : Usually Ships in 5 - 7 Working Days Shipping Weight : 2 Kg
| Model | 1756-IM16I | |
| Inputs | 16 individually isolated | |
| Voltage category | 240V AC 50/60 Hz | |
| Operating voltage range | 159 265V AC, 47 63 Hz? | |
| Input voltage, nom | 240V AC 50/60 Hz | |
| Input delay time (screw to backplane) Off to On ON to Off | Hardware delay: 10 ms max + filter time User-selectable filter time: 1 or 2 ms Hardware delay: 8 ms max + filter time User-selectable filter time: 9 or 18 ms | |
| Current draw @ 5.1V | 100 mA | |
| Current draw @ 24V | 3 mA | |
| Total backplane power | 0.58 W | |
| Power dissipation, max | 5.8 W @ 60 ?C (140 ?F) | |
| Thermal dissipation | 19.78 BTU/hr | |
| Off-state voltage, max | 40V | |
| Off-state current, max | 2.5 mA | |
| On-state current, min | 5 mA @ 159V AC, 60 Hz | |
| On-state current, max | 13 mA @ 265V AC, 60 Hz | |
| On-state voltage | 159 265V AC, 47 63Hz @ 30 ?C (86 ?F) all channels ON 159 265V AC, 47 63Hz @ 40 ?C (104 ?F) 8 points ON 159 253V AC, 47 63Hz @ 45 ?C (113 ?F) all channels ON 159 242V AC, 47 63Hz @ 60 ?C (140 ?F) all channels ON | |
| Inrush current, max | 250 mA | |
| Input impedance, max | 20.38 k @ 265V AC, 60 Hz | |
| Cyclic update time | 200 s 750 ms | |
| Change of state | Software configurable | |
| Timestamp of inputs | ?200 s | |
| Isolation voltage | 250V (continuous), basic insulation type, inputs-to-backplane, and input-to-input Routine tested @ 1350V AC for 2 s | |
| Module keying | Electronic, software configurable | |
| Removable terminal block | 1756-TBCH 1756-TBS6H | |
| RTB keying | User-defined mechanical | |
| Slot width | 1 | |
| Wire category | 1? | |
| North American temperature code | T4 | |
| IEC temperature code | T4 | |
| Enclosure type | None (open-style) | |
(1) UL certification for 240V 50/60 Hz nominal. Rockwell Automation specified to the following:
159 265V AC, 47 63Hz @ 30 ?C (86 ?F) all channels on
159 265V AC, 47 63Hz @ 40 ?C (104 ?F) 8 points on
159 253V AC, 47 63Hz @ 45 ?C (113 ?F) all channels on
159 242V AC, 47 63Hz @ 60 ?C (140 ?F) all channels on.
(2) Use this conductor category information for planning conductor routing as described in the system-level installation manual. See the Industrial Automation Wiring and Grounding
Guidelines, publication 1770-4.1.
Your Can Likes
- 1794-OB16PXT New Allen Bradley FLEX I/O Discrete Output Module
- $1,534.00 $752.00
Save: 51% off
- CC-PAIX01 New Honeywell Analog Input Module
- $3,688.00 $1,807.00
Save: 51% off
- TCSESM043F2CS0 New Schneider Ethernet TCP/IP Managed Switch
- $483.00 $237.00
Save: 51% off
- 1786-RPFM New Allen Bradley Ring Repeater
- $971.00 $578.00
Save: 40% off